Nr.
Item to check
Fulfilled (Yes / No)?
Comment
7.
Verify that:
n
Address setting is correct
n
Assignment of signal inputs is complete
n
Assignment of signal outputs is complete
n
Assignment of unused inputs is complete
n
All terminal blocks are plugged
8.
Verify that correct firmware versions are used for
dependent non-safety components, like CM579-PNIO
(V2.6.5.1 or higher), CI50x (V3.2.0 or higher) and
PM5xx CPUs (V2.2.1 or higher).
Contact ABB technical support if needed.
Reviewer(s):
Machine/Application <ID>:
Signature:
Date:
6.4 Checklist for operation, maintenance and repair
Nr.
Item to check
Fulfilled (Yes / No)?
Comment
1.
Make sure that all Safety modules are properly
placed on their positions at the terminal base (Safety
CPU) or terminal units (Safety I/Os) and stable con-
tact between terminals and safety modules is
assured.
2
Check that proper temperature monitoring measures
(e.g., temperature sensors could be placed in the
control cabinet and connected to AI581-S safety
analog input channels) are implemented in the control
cabinet where AC500-S safety modules are placed, if
the operating temperature range for AC500-S Safety
PLC cannot be guaranteed.
Note:
Safety digital outputs of DX581-S module have
internal built-in overtemperature protection and
always deliver fail-safe “0” values in case of overtem-
perature.
Checklists for AC500-S Commissioning
Checklist for operation, maintenance and repair
30.03.2017