3.5.6 Parameterization
The arrangement of the parameter data is performed by your system configuration software PS501 Control
Builder Plus V2.2.1 (or newer) / ABB Automation Builder 1.0 (or newer). ABB GSDML file for PROFINET
devices can be used to configure AI581-S parameters in 3
rd
party PROFINET F-Host systems.
The parameter setting directly influences the functionality of modules and reachable SIL (IEC 61508 ed. 2
and IEC 62061) and PL (ISO 13849).
No.
Name
Values
Default
1
Check supply
“On”, “Off”
“On”
2
Configuration
“Not used”, “1 channel (0 … 20 mA)”, “1 channel
(4 … 20 mA)”, “2 channel (4 … 20 mA)”
“Not used”
3
Noise rejection
“50 Hz”, “60 Hz”, “None”
“50 Hz”
4
Tolerance range
(used only for “2
channel
(4 … 20 mA)” mode)
“4 %”, “5 %”, “6 %”, “7 %”, “8 %”, “9 %”, “10 %”,
“11 %”, “12 %”
“4 %”
5
Used value (Min /
Max) (used only for
“2 channel
(4 … 20 mA)” mode)
“Minimum”, “Maximum”
“Minimum”
3.5.7 Circuit examples
Examples of electrical connections and reachable SIL (CL) (IEC 61508 ed. 2 and IEC 62061), Category (EN
954) and PL (ISO 13849) with AI581-S module are presented below.
NOTICE!
Whenever DC = High is used in the circuit examples for safety analog inputs, the following measure
from ISO 13849-1 [10] is used in AI581-S module: Cross monitoring of input signals and intermediate
results within the logic (L), and temporal and logical software monitor of the program flow and detec-
tion of static faults and short circuits (for multiple I/O).
Whenever DC = Medium is used in the circuit examples for safety analog inputs, any of the measures
for input devices with DC
³
90 % can be used from ISO 13849-1 [10].
AC500-S Safety Modules
AI581-S analog safety input module > Circuit examples
30.03.2017
AC500-S
144