A.3
Environmental tests
Storage
IEC 60068-2-1 Test Ab: cold withstand test -40 °C / 16 h
IEC 60068-2-2 Test Bb: dry heat withstand test +85 °C / 16 h
Humidity
IEC 60068-2-30 Test Dd: Cyclic (12 h / 12 h) Damp-Heat Test 55 °C, 93% relative
humidity / 25 °C, 95 % relative humidity, 6 cycles
IEC 60068-2-78, Stationary Humidity Test: 40 °C, 93 % relative humidity, 240 h
Insulation test
IEC 61131-2
Vibration resistance
IEC 61131-2 / IEC 60068-26: 5 Hz … 500 Hz, 2 g (with SD memory card inserted in
PM5xx CPU)
IEC 60068-2-64: 5 Hz … 500 Hz, 4 g rms
Schock resistance
IEC 60068-2-27: all 3 axes 15 g, 11 ms, half-sinusoidal
EMC Immunity
Electrostatic discharge (ESD)
Data
Value Unit
Electrostatic voltage in case of air discharge
8 kV
Electrostatic voltage in case of contact discharge
6 kV
Fast transient interference voltages (burst)
Data
Value Unit
Supply voltage units (DC)
4 kV
Digital inputs/outputs (24 V DC)
2 kV
Analog inputs/outputs
2 kV
Communication lines shielded
2 kV
I/O supply (DC-out)
2 kV
High energy transient interference voltages (surge) - Common Mode (CM)
Data
Value Unit
Supply voltage units (DC)
1 kV
Digital inputs/outputs (24 V DC)
1 kV
Analog inputs/outputs
1 kV
Communication lines shielded
1 kV
I/O supply (DC-out)
0.5 kV
High energy transient interference voltages (surge) - Differential Mode (DM)
Data
Value Unit
Supply voltage units (DC)
0.5 kV
Digital inputs/outputs (24 V DC)
0.5 kV
System data for AC500-S-XC
30.03.2017
AC500-S
450