DiagCode
State Name
State Description and Output Setting
8003
Wait for Reset Safety demand or errors have been detected and are now cleared. Oper-
ator acknowledgment by Reset required.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
8005
Safe
Safety function activated.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
8011
Muting For-
ward Start 1
Muting forward sequence is in starting phase after rising trigger of
MutingSwitch 11. Monitoring of DiscTime11_12 is activated. Monitoring of
MaxMutingTime is activated.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
8311
Muting For-
ward Start 2
Muting forward sequence is in starting phase after rising trigger of
MutingSwitch 12. Monitoring of DiscTime11_12 is activated. Monitoring of
MaxMutingTime is activated.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
8012
Muting For-
ward Active 1
Muting forward sequence is active either:
- After rising trigger of the second entry MutingSwitch 12 or 11 has been
detected.
- When both MutingSwitch 11 and 12 have been actuated in the same
cycle.
Monitoring of DiscTime11_12 is stopped. Monitoring of MaxMutingTime is
activated, when transition came directly from state 8000.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = TRUE
Error = FALSE
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib