![ABB AC500-S Safety User Manual Download Page 44](http://html.mh-extra.com/html/abb/ac500-s/ac500-s_safety-user-manual_2916044.webp)
Error
class
Compo-
nent or
Inter-
face
Device Module
Channel
Error
Error text
Remedy
E2
1 … 4
255
30
2
19
Checksum
error has
occured in
Safety PLC.
Restart Safety PLC. If this
error persists, replace
Safety PLC.
E2
1 … 4
255
30
2
17
Internal error
Contact ABB technical sup-
port. Replace Safety PLC.
E2
1 … 4
255
30
2
13
Flash write
error
Restart Safety PLC. If this
error persists, replace
Safety PLC. Contact ABB
technical support.
E2
1 … 4
255
30
2
37
Cycle time
error in Safety
PLC
Check Safety PLC
watchdog time.
E2
1 … 4
255
30
2
10
Internal error
Contact ABB technical sup-
port. Replace Safety PLC.
E2
1 … 4
255
30
2
25
Internal error
Contact ABB technical sup-
port. Replace Safety PLC.
E2
1 … 4
255
30
2
42
Internal error
Contact ABB technical sup-
port. Replace Safety PLC.
E2
1 … 4
255
30
2
1
Internal error
Contact ABB technical sup-
port. Replace Safety PLC.
E2
1 … 4
255
30
2
3
Internal error
Contact ABB technical sup-
port. Replace Safety PLC.
E2
1 … 4
255
30
2
54
Internal error
Contact ABB technical sup-
port. Replace Safety PLC.
E2
1 … 4
255
30
2
38
Internal error
Contact ABB technical sup-
port. Replace Safety PLC.
E2
1 … 4
255
30
2
52
Internal error
Contact ABB technical sup-
port. Replace Safety PLC.
E3
1 or 9
255
30
1
26
Error in config-
uration data,
Safety PLC
cannot read
configuration
data
Create new configuration
data
E4
1 or 9
255
30
2
26
No or wrong
configuration
data from
PM5x, run
state not pos-
sible
Create correct boot project
at PM5x
AC500-S Safety Modules
SM560-S Safety CPU > Diagnosis and LED status display
30.03.2017
AC500-S