![ABB AC500-S Safety User Manual Download Page 152](http://html.mh-extra.com/html/abb/ac500-s/ac500-s_safety-user-manual_2916152.webp)
Allowed interruptions of power supply, according to EN 61131-2
Data
Value Unit
DC supply interruptions
< 10 ms
Time between 2 DC supply interruptions, PS2
> 1 s
Environmental conditions
Data
Value Unit
Operating temperature*
0 ... +60 °C
Storage temperature
–40 ... +85 °C
Transport temperature
–40 ... +85 °C
Humidity without condensation
max. 95 %
Operating air pressure
> 800 hPa
Storage air pressure
> 660 hPa
Operating altitude
< 2000 m above sea
level
Storage altitude
< 3500 m above sea
level
* Extended temperature ranges (below 0 °C and above +60 °C) can be supported in special versions of
Appendix “System data for AC500-S-XC” on page 446
)
Creepage distances and clearances
The creepage distances and clearances meet the overvoltage category II, pollution degree 2.
Power supply units
For the supply of modules, power supply units according to PELV/SELV specifications must be used.
Electromagnetic compatibility
Ä
TÜV Report [2]
AC500-S Safety Modules
AI581-S analog safety input module > Technical data
30.03.2017
AC500-S
152