Error
class
Compo-
nent or
Inter-
face
Device Module
Channel
Error
Error text
Remedy
E3
14
1..10
0
0..15
28
Channel cross-
talk error
Check I/O module wiring.
Restart I/O module, if
needed. If this error per-
sists, replace I/O module.
E3
14
1..10
2
0..7
13
Module 0:
Channel test
pulse cross-
talk error
Module 2:
Channel read-
back error
Check I/O module wiring.
Restart I/O module, if
needed. If this error per-
sists, replace I/O module.
E3
14
1..10
2
0..7
18
Channel cross-
talk error
Check I/O module wiring.
Restart I/O module, if
needed. If this error per-
sists, replace I/O module.
Table 6: List of error messages for Safety I/O modules (channel or module reintegration is not possible)
Error
class
Compo-
nent or
Inter-
face
Device Module
Channel
Error
Error text
Remedy
E3
14
1..10
31
31
28
F-Parameter
configuration
and address
switch value
do not match.
Check I/O module F-
Parameter configuration
and module address switch
value.
E3
14
1..10
31
31
26
Parameter
value
Check master or configura-
tion
E3
14
1..10
31
31
19
Checksum
error in the I/O
module
Non-safety I/O: Replace I/O
module
Safety I/O: Check safety
configuration and CRCs for
I- and F-Parameters.
E3
14
1..10
31
31
18
Plausibility
check failed
(iParameter)
Check configuration