Memory
Data
Value Unit
User Program memory
1 MByte
User Data memory (thereof 120 kBytes saved)
1 MByte
Minimum Performance
Data
Value Unit
Cycle time Binary
0.05 µs/Instruction
Cycle time Word
0.06 µs/Instruction
Cycle time floating-point
0.50 µs/Instruction
Voltages, according to EN 61131-2
Data
Value Unit
Process and supply voltage (without ripple)
24 ( – 15 %, +20 %) V DC
Absolute limits (including ripple)
19.2 ... 30 V
Ripple
< 5 %
Protection against reverse polarity
10 s
DANGER!
Exceeding the maximum process or supply voltage range (< –35 V DC or > +35 V DC) could lead to
unrecoverable damage of the system.