![ABB AC500-S Safety User Manual Download Page 328](http://html.mh-extra.com/html/abb/ac500-s/ac500-s_safety-user-manual_2916328.webp)
DiagCode
State Name
State Description and Output Setting
C004
Reset Error 4
Static Reset condition detected in state C020.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
C005
Reset Error 5
Static Reset condition detected in state 8006.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
C006
Reset Error 6
Static Reset condition detected in state C000.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
C007
Reset Error 7
Static Reset condition detected in state 8013.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = TRUE
Error = TRUE
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017
AC500-S
328