DiagCode
State Name
State Description and Output Setting
8014
Muting For-
ward Step 1
Muting forward sequence is active. MutingSwitch21 is the first exit switch
actuated. Monitoring of DiscTime21_22 is started.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = TRUE
Error = FALSE
8314
Muting For-
ward Step 2
Muting forward sequence is active. MutingSwitch22 is the first exit switch
actuated. Monitoring of DiscTime21_22 is started.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = TRUE
Error = FALSE
8021
Muting For-
ward Active 2
Muting forward sequence is still active. Both MutingSwitch21 and 22 are
actuated, the monitoring of DiscTime21_22 is stopped.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = TRUE
Error = FALSE
8122
Muting Back-
ward Start 1
Muting backward sequence is in starting phase after rising trigger of
MutingSwitch21. Monitoring of DiscTime21_22 is activated. Monitoring of
MaxMutingTime is activated.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
8422
Muting Back-
ward Start 2
Muting backward sequence is in starting phase after rising trigger of
MutingSwitch22. Monitoring of DiscTime21_22 is activated. Monitoring of
MaxMutingTime is activated.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib