Signal voltage
Data
Value Unit
Input signal voltage
24 V DC
Signal 0
–3 … +5 V
Undefined signal
> +5 … < +15 V
Signal 1
+15 … +30 V
Input current per channel
Data
Value Unit
Input v24 V, typically
7 mA
Input v5 V
< 1 mA
Input v15 V
> 4 mA
Input v30 V
< 8 mA
Cable length
Data
Value Unit
Max. cable length, shielded
1000 m
Max. cable length, unshielded
600 m
3.4.9.2
Technical data of safety digital outputs
DANGER!
Exceeding the maximum process or supply voltage range (< –35 V DC or > +35 V DC) could lead to
unrecoverable damage of the system.