IX - Index for access via CANopen with s = Subindex, depends on number and type of
analog modules
SX - Subindex for access via EtherCAT with Index 6000h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Addr.
Name
Bytes
Function
IX
SX
+0
AI 0
2
Analog value channel 0
6401h/s
01h
+2
AI 1
2
Analog value channel 1
6401h/s+1
02h
No byte of the output area is used by the module.
3.9.1 Technical data
Order no.
031-1BB90
Type
SM 031
Module ID
0403 1543
Current consumption/power loss
Current consumption from backplane bus
85 mA
Power loss
1.1 W
Technical data analog inputs
Number of inputs
2
Cable length, shielded
200 m
Rated load voltage
DC 24 V
Current consumption from load voltage L+ (without load)
30 mA
Voltage inputs
-
Min. input resistance (voltage range)
10 MΩ
Input voltage ranges
-80 mV ... +80 mV
Operational limit of voltage ranges
±0.3%
Operational limit of voltage ranges with SFU
±0.1%
Basic error limit voltage ranges
±0.25%
Basic error limit voltage ranges with SFU
±0.05%
Destruction limit voltage
max. 20V
Current inputs
-
Max. input resistance (current range)
-
Input current ranges
-
Operational limit of current ranges
-
Operational limit of current ranges with SFU
-
Basic error limit current ranges
-
Input area
Output area
VIPA System SLIO
Analog Input
031-1BB90 - AI 2x16Bit TC > Technical data
HB300 | SM-AIO | | en | 17-05
96