3.27.7.2.3
Set Frame
In the module you can combine some measurands to one data package (Frame), which
. With
‘Set Frame’
a Frame can be built.
Request
Byte
Value
Description
B0
0x30
n
Bit 3 ... 0: Error code (not relevant)
n
Bit 6 ... 4: 011 Telegram type
‘Set Frame’
n
Bit 7: 0 fix reserved
B1
?
n
B2
0x0?
n
Length user data: 1 byte each measurand
n
DS-ID
here fix 0
B3
0x00
n
Common status (not relevant)
D00
?
n
1 byte each measurand regarding that the measured values do not exceed the total
length of 12 byte. Here, the format of the measured values is taken into account.
Chapter 3.27.6 ‘Measurands’ on page 316
...
D11
Response
Byte
Value
Description
B0
0x30
n
‘Status communication’ on page 319
n
Bit 6 ... 4: 011 Telegram type
‘Set Frame’
n
Bit 7: 0 fix reserved
B1
...
n
FR-ID
of the Frame from the request
B2
...
n
Length of the user data from the request
n
DS-ID
here fix 0
B3
...
n
D00
...
n
User data from the request
...
D11
Overview
VIPA System SLIO
Analog Input
031-1PA00 - AI1x 3Ph 230/400V 1A > Process data communication
HB300 | SM-AIO | | en | 17-05
323