Byte
Bit 7 ... 0
0
n
Bit 3 ... 0: module class
–
0101b analog module
n
Bit 4: set at channel information present
n
Bit 7 ... 5: reserved
Byte
Bit 7 ... 0
0
n
Bit 2 ... 0: reserved
n
Bit 3: set at internal diagnostics buffer overflow
n
Bit 4: set at internal communication error
n
Bit 7 ... 5: reserved
Byte
Bit 7 ... 0
0
n
Bit 6 ... 0: Channel type
–
70h: Digital input
–
71h: Analog input
–
72h: Digital output
–
73h: Analog output
–
74h: Analog input/-output
–
76h: Counter
n
Bit 7: reserved
Byte
Bit 7 ... 0
0
Number of diagnostic bits per channel (here 08h)
Byte
Bit 7 ... 0
0
Number of channels of a module (here 04h)
Byte
Bit 7 ... 0
0
n
Bit 0: set at error in channel group 0
n
Bit 1: set at error in channel group 1
n
Bit 2: set at error in channel group 2
n
Bit 3: set at error in channel group 3
n
Bit 7 ... 4: reserved
Byte
Bit 7 ... 0
0
Channel-specific error channel x:
n
Bit 0: set at configuring/parameter assignment error
n
Bit 2 ... 1: reserved
n
Bit 3: set at short-circuit to ground
n
Bit 7 ... 4: reserved
MODTYP Module informa-
tion
ERR_D Diagnostic
CHTYP Channel type
NUMBIT Diagnostic bits
NUMCH Channels
CHERR Channel error
CH0ERR ... CH3ERR
Channel-specific
VIPA System SLIO
Analog Output
032-1BD70 - AO 4x12Bit ±10V > Diagnostic data
HB300 | SM-AIO | | en | 17-05
389