Order no.
032-1CB40
Operating temperature
0 °C to 60 °C
Storage temperature
-25 °C to 70 °C
Certifications
UL certification
in preparation
KC certification
yes
4.11.2
Parameter data
DS - Record set for access via CPU, PROFIBUS and PROFINET
IX - Index for access via CANopen
SX - Subindex for access via EtherCAT with Index 3100h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Name
Bytes
Function
Default
DS
IX
SX
RES0
1
reserved
00h
00h
3100h
01h
WIBRK_EN
1
Wire-break recognition
00h
00h
3101h
02h
CH0FN
1
Function number channel 0
31h
80h
3102h
03h
CH1FN
1
Function number channel 1
31h
81h
3103h
04h
Byte
Bit 7 ... 0
0
n
Bit 0: Wire-break recognition channel 0 (1: on)
n
Bit 1: Wire-break recognition channel 1 (1: on)
n
Bit 7 ... 2: reserved
Please consider with enabled wire break recognition with the output
range 0 ... 20mA, when the current goes below of 40µA (100 Digits), this
can may lead to sporadic wire break messages!
In the following there are the measuring ranges with corresponding function number
listed, which were supported by the analog module. With FFh the corresponding channel
is deactivated. The formulas listed here allow you to transform an evaluated measuring
value (digital value) to a value assigned to the measuring range (analog value) and vice
versa.
WIBRK_EN Wire-break
recognition
CHxFN Function number
channel x
VIPA System SLIO
Analog Output
032-1CB40 - AO 2x16Bit 0(4)...20mA > Parameter data
HB300 | SM-AIO | | en | 17-05