As long as no parameters have been sent from the head station to
the module after a power cycle, default values are transmitted by the
module during a read access and not the parameters stored in the
module.
–
After transferring the parameters to the module the status bits are
reset and the measurement is interrupted for a short time!
–
Please note when at least one phase is de-activated, the parameters
PF_MIN and VRMS_MIN are ignored and set to "0".
–
On error in the parametrization the MF LED blinks and you receive an
error message.
‘Status communication’ on page 319
CFG
Bit
Name
Description
Default
0
reserved
0
1
Write Protect
*)
Write protection bit for parameterization via Web server
0: Write Protect de-activated
1: Write Protect activated
Please see the following note!
1
*)
2
reserved
0
3
Phase 1
Measurement phase L1
0: Measurement is activated
1: Measurement is de-activated
0
4
Phase 2
Measurement phase L2
0: Measurement is activated
1: Measurement is de-activated
0
5
Phase 3
Measurement phase L3
0: Measurement is activated
1: Measurement is de-activated
0
6
Data type
Data type of the measured values in the user data
0: Integer (INT)
1: 32bit floating point (FLOAT) DIN IEEE 754
0
7
Byteorder
Data type of the measured values in the user data
0: Big-Endian: Byte order: high byte, low byte
1: Little-Endian: Byte order: low byte, high byte
0
*) Access to the
‘Write Protect’
parameter is only possible via the Web server of the head module (not via GSD or GSDML).
Data type
VIPA System SLIO
Analog Input
031-1PA00 - AI1x 3Ph 230/400V 1A > Parameter data
HB300 | SM-AIO | | en | 17-05
315