Output range
(funct. no.)
Current
(I)
Decimal
(D)
Hex
Range
Formulas
0 ... 20mA
Siemens
S7 format
(31h)
23.52mA
32511
7EFFh
overrange
20mA
27648
6C00h
nominal range
10mA
13824
3600h
0mA
0
0000h
Not possible, is limited to 0mA.
underrange
0 ... 20mA
Siemens
S5 format
(41h)
25.00mA
20480
5000h
overrange
20mA
16384
4000h
nominal range
10mA
8192
2000h
0mA
0
0000h
Not possible, is limited to 0mA.
underrange
Output range
(funct. no.)
Current
(I)
Decimal
(D)
Hex
Range
Formulas
4 ... 20mA
Siemens
S7 format
(30h)
22.81mA
32511
7EFFh
overrange
20mA
27648
6C00h
nominal range
12mA
13824
3600h
4mA
0
0000h
0mA
-6912
E500h
underrange
4 ... 20mA
Siemens
S5 format
(40h)
24.00mA
20480
5000h
overrange
20mA
16384
4000h
nominal range
12mA
8192
2000h
4mA
0
0000h
0mA
-4096
F000h
underrange
4.8.3 Diagnostic data
So this module does not support interrupt functions, the diagnostics data serve for infor-
mation about this module. On error the corresponding channel LED of the module is acti-
vated and the error is registered in the diagnostics data.
The following errors are listed in the diagnostics data:
n
Error in project engineering / parameterization
n
Wire-break (if parameterized)
0 ... 20mA
4 ... 20mA
VIPA System SLIO
Analog Output
032-1BD40 - AO 4x12Bit 0(4)...20mA > Diagnostic data
HB300 | SM-AIO | | en | 17-05
379