Order no.
032-1BB30
Storage temperature
-25 °C to 70 °C
Certifications
UL certification
yes
KC certification
yes
4.4.2 Parameter data
DS - Record set for access via CPU, PROFIBUS and PROFINET
IX - Index for access via CANopen
SX - Subindex for access via EtherCAT with Index 3100h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Name
Bytes
Function
Default
DS
IX
SX
RES0
1
reserved
00h
00h
3100h
01h
SHORT_EN
1
Short-circuit recognition
00h
00h
3101h
02h
CH0FN
1
Function number channel 0
10h
80h
3102h
03h
CH1FN
1
Function number channel 1
10h
81h
3103h
04h
Byte
Bit 7 ... 0
0
n
Bit 0: Short-circuit recognition channel 0 (1:on)
n
Bit 1: Short-circuit recognition channel 1 (1:on)
n
Bit 7 ... 2: reserved
In the following there are the measuring ranges with corresponding function number
listed, which were supported by the analog module. With FFh the corresponding channel
is deactivated.
The formulas listed here allow you to transform an evaluated measuring value (digital
value) to a value assigned to the measuring range (analog value) and vice versa.
SHORT_EN Short-circuit
recognition
CHxFN Function number
channel x
VIPA System SLIO
Analog Output
032-1BB30 - AO 2x12Bit 0...10V > Parameter data
HB300 | SM-AIO | | en | 17-05
344