RUN
MF
Description
green
red
●
○
Bus communication is OK
Module status is OK
●
●
Bus communication is OK
Module status reports an error
○
●
Bus communication is not possible
Module status reports an error
○
○
Error at bus power supply
X
B
Error in configuration
Chapter 2.8 ‘Trouble shooting -
>U
red
○
Voltage in the parametrized range
●
Voltage limit value exceeded
<U
red
○
Voltage in the parametrized range
●
Voltage limit value undershot
(omitted in 1-phase operation)
>I
red
○
Current in the parametrized range
●
Current limit value exceeded
<cos
red
○
Phase shift cos
j
in the parametrized range
●
Phase shift cos
j
limit value undershot
(omitted in 1-phase operation)
TEMP
red
○
Temperature in the parametrized range
●
Temperature limit value exceeded
P
green
B
P: Power-proportional
blinks with increasing frequency proportional to
the active power at 20 pulses/Wh. The current
transformer factor is not considered.
on: ● | off: ○ | blinking: B | not relevant: X
Status indication
VIPA System SLIO
Analog Input
031-1PA00 - AI1x 3Ph 230/400V 1A
HB300 | SM-AIO | | en | 17-05
303