CAUTION!
Do not exchange current and voltage connections!
Please note when connecting, that the current and voltage paths are not
exchanged! The module will be destroyed by directly connecting one
phase to a low-resistance current connector!
CAUTION!
Use current transformer with max. 1A!
You may only use current transformer with max. current of 1A! Please
consider the data sheet of your current transformer!
CAUTION!
All phases of one supply grid!
Please note that the phases to be measured must be from the same
supply grid!
Reset energy counters after installation!
As soon as the module is supplied by the DC 24V power section supply,
the measurement is started and the counting of the energy counters is
continued with the retentive stored counter values. The measurement is
not interrupted by STOP or RESET of the CPU respectively the bus cou-
pler. After installing the module the energy counters should be reset by
CMD-Frame.
Chapter 3.27.7.2.5 ‘CMD Frame’ on page 327
VIPA System SLIO
Analog Input
031-1PA00 - AI1x 3Ph 230/400V 1A > Connection
HB300 | SM-AIO | | en | 17-05