Status
Designation
0x05
Error:
Frame
not defined
0x06
Error: Measurand not available
Chapter 3.27.6 ‘Measurands’ on page 316
0x07
Error:
‘CMD Frame’
- Command could not be executed
0x08
Error:
‘Set Frame’
- Frame definition is not valid (Set Frame)
0x09
Error: Telegram type not available - invalid request
0x0A
Error: Parameter - the last parameter set was not valid
0x0E
External error - Please contact our support
0x0F
Internal error - Please contact our support
On an
internal error
(0x0F) all the measurements are stopped and a
Reset of the module to default parameters is triggered! Here all
counter values and Frame definitions are deleted!
By specifying the
Telegram type
the content of the responded data is defined. The fol-
lowing telegram types are available:
Type
Designation
Page
0x00
‘Zero Frame’
: Accessing
Frame 0
0x01
‘Read Value’
: Read the measured value of a measurand
0x02
‘Read Frame’
: Read a previously defined data package
(Frame)
0x03
‘Set Frame’
: Define the data areas of a data package (Frame)
0x04
‘CMD Frame’
: Send a command
The measured values of one measurement are accessible in the module via one DS-ID.
Length of user data are specified from D00 ... D11: On error no user data are transferred
i.e. the length of the user data is 0 and the module returns an error ID.
Range of values: 0 ... 12
With this byte you get an overview of possible error messages. With
you get detailed information about an error.
n
Bit 0: Frequency
F_MAX
exceeded
n
Bit 1: Frequency
F_MIN
undershot
n
Bit 2: Temperature
T_MAX
exceeded
n
Bit 3: Voltage
VRMS_MAX
exceeded
n
Bit 4: Voltage
VRMS_MIN
undershot
n
Bit 5: Efficiency
PF_MIN
undershot
n
Bit 6: Current
IRMS_MAX
exceeded
n
Bit 7: reserved
Telegram types
Data set ID - DS-ID
Length of the user data
Common status
VIPA System SLIO
Analog Input
031-1PA00 - AI1x 3Ph 230/400V 1A > Process data communication
HB300 | SM-AIO | | en | 17-05