3.26.2
Parameter data
DS - Record set for access via CPU, PROFIBUS and PROFINET
IX - Index for access via CANopen
SX - Subindex for access via EtherCAT with Index 3100h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Name
Bytes
Function
Default
DS
IX
SX
DIAG_EN
1
Diagnostic
1
00h
00h
3100h
01h
WIBRK_EN
1
Wire break recognition
1
00h
00h
3101h
02h
TEMPCNF
1
Temperature system
00h
01h
3102h
03h
SUPR
1
Interference frequency suppression
02h
01h
3103h
04h
CH0FN
1
Function number channel 0
50h
80h
3104h
05h
CH1FN
1
Function number channel 1
50h
81h
3105h
06h
CH2FN
1
Function number channel 2
50h
2
82h
3106h
07h
CH3FN
1
Function number channel 3
50h
2
83h
3107h
08h
1) This record set may only be transferred at STOP state.
2) with 2 channel operation FFh
Byte
Bit 7 ... 0
0
n
Diagnostic interrupt
–
00h: disabled
–
40h: enabled
n
Here you can enable respectively disable the diagnostic interrupt.
Byte
Bit 7 ... 0
0
n
Bit 0: Wire break recognition channel 0 (1: on)
n
Bit 1: Wire break recognition channel 1 (1: on)
n
Bit 2: Wire break recognition channel 2 (1: on)
n
Bit 3: Wire break recognition channel 3 (1: on)
n
Bit 7 ... 4: reserved
Byte
Bit 7 ... 0
0
n
Bit 1, 0: Temperature system
–
00: °C
–
01: °F
–
10: K
n
Bit 7 ... 2: reserved
DIAG_EN Diagnostic inter-
rupt
WIBRK_EN Wire break
recognition
TEMPCNF Temperature
system
VIPA System SLIO
Analog Input
031-1LD80 - AI 4x16Bit R/RTD > Parameter data
HB300 | SM-AIO | | en | 17-05
295