With a resolution of 12bit plus sign bit, the least significant bits (3bit) are not relevant.
The algebraic sign bit is represented by Bit 15. Here it is essential:
n
Bit 15 = "0":
à
positive value
n
Bit 15 = "1":
à
negative value
4.3 Output ranges and function numbers
In the following there are the output ranges listed with function number, which were sup-
ported by the corresponding analog module. The here listed formulas allow you to trans-
form a value (digital value) to an analog value and vice versa.
Voltage
Output range
(funct. no.)
Voltage
(U)
Decimal
(D)
Hex
Range
Formulas
0 ... 10V
Siemens
S7 format
(10h)
11,76V
32511
7EFFh
overrange
10V
27648
6C00h
nominal range
5V
13824
3600h
0V
0
0000h
Not possible, is limited to 0V.
underrange
0 ... 10V
Siemens
S5 format
(20h)
12,5V
20480
5000h
overrange
10V
16384
4000h
nominal range
5V
8192
2000h
0V
0
0000h
Not possible, is limited to 0V.
underrange
Resolution
Sign bit (SG)
General
Output ranges
0 ... 10V
VIPA System SLIO
Analog Output
Output ranges and function numbers