Event
Process
interrupt
Diagnostics
interrupt
parameterizable
Measuring range underflow
-
X
-
Limit overflow
X
-
X
Limit underflow
X
-
X
Diagnostic buffer overflow
-
X
-
Communication error
-
X
-
Process interrupt lost
-
X
-
So you may react to asynchronous events, there is the possibility to activate a process
interrupt. A process interrupt interrupts the linear program sequence and jumps
depending on the master system to a corresponding Interrupt routine. Here you can react
to the process interrupt accordingly.
With CANopen the process interrupt data a transferred via an emergency telegram.
Operating with CPU, PROFIBUS and PROFINET the process interrupt data were trans-
ferred via diagnostics telegram.
SX - Subindex for access via EtherCAT with Index 5000h
More can be found in the according manual of your bus coupler.
Name
Bytes
Function
Default
SX
PRIT_OL
1
Limit overflow channel x
00h
02h
PRIT_UL
1
Limit underflow channel x
00h
03h
PRIT_US
2
µs ticker
00h
04h ... 05h
Byte
Bit 7 ... 0
0
n
Bit 0: Limit overflow channel 0
n
Bit 1: Limit overflow channel 1
n
Bit 7 ... 2: reserved
Byte
Bit 7 ... 0
0
n
Bit 0: Limit underflow channel 0
n
Bit 1: Limit underflow channel 1
n
Bit 7 ... 2: reserved
Byte
Bit 7 ... 0
0 ... 1
Value of the µs ticker at the moment of the diagnostic.
µs ticker
In the SLIO module there is a 32 bit timer (µs ticker). With PowerON the timer starts
counting with 0. After 2
32
-1µs the timer starts with 0 again. PRIT_US represents the lower
2 byte of the µs ticker value (0 ... 2
16
-1).
Process interrupt
PRIT_OL Limit overflow
PRIT_UL Limit underflow
PRIT_US µs ticker
VIPA System SLIO
Analog Input
031-1CB30 - AI 2x16Bit 0...10V > Diagnostics and interrupt
HB300 | SM-AIO | | en | 17-05