3.14.2
Parameter data
DS - Record set for access via CPU, PROFIBUS and PROFINET
IX - Index for access via CANopen
SX - Subindex for access via EtherCAT with Index 3100h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Name
Bytes
Function
Default
DS
IX
SX
SUPR
2
Interference frequency suppression
0000h
01h
3100h,
3101h
01h
CH0FN
1
Function number channel 0
31h
80h
3102h
02h
CH1FN
1
Function number channel 1
31h
81h
3103h
03h
CH2FN
1
Function number channel 2
31h
82h
3104h
04h
CH3FN
1
Function number channel 3
31h
83h
3105h
05h
CH4FN
1
Function number channel 4
31h
84h
3106h
06h
CH5FN
1
Function number channel 5
31h
85h
3107h
07h
CH6FN
1
Function number channel 6
31h
86h
3108h
08h
CH7FN
1
Function number channel 7
31h
87h
3109h
09h
Byte
Bit 15 ... 0
0
n
Bit 0, 1: Interference frequency suppression channel 0
n
Bit 2, 3: Interference frequency suppression channel 1
n
Bit 4, 5: Interference frequency suppression channel 2
n
Bit 6, 7: Interference frequency suppression channel 3
n
Bit 8, 9: Interference frequency suppression channel 4
n
Bit 10, 11: Interference frequency suppression channel 5
n
Bit 12, 13: Interference frequency suppression channel 6
n
Bit 14, 15: Interference frequency suppression channel 7
–
00: deactivated
–
01: 60Hz
–
10: 50Hz
In the following there are the measuring ranges with corresponding function number
listed, which were supported by the analog module. With FFh the corresponding channel
is deactivated. The formulas listed here allow you to transform an evaluated measuring
value (digital value) to a value assigned to the measuring range (analog value) and vice
versa.
SUPR Interference fre-
quency suppression
CHxFN Function number
channel x
VIPA System SLIO
Analog Input
031-1BF60 - AI 8x12Bit 0(4)...20mA > Parameter data
HB300 | SM-AIO | | en | 17-05
157