3.13.2
Parameter data
DS - Record set for access via CPU, PROFIBUS and PROFINET
IX - Index for access via CANopen
SX - Subindex for access via EtherCAT with Index 3100h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Name
Bytes
Function
Default
DS
IX
SX
DIAG_EN
1
Diagnostics
1
00h
00h
3100h
01h
WIBRK_EN
1
Wire break recognition
1
00h
00h
3101h
02h
LIMIT_EN
1
Limit value monitoring
1
00h
00h
3102h
03h
RES3
1
reserved
00h
00h
3103h
04h
TEMPCNF
1
Temperature system
00h
01h
3104h
05h
SUPR
1
Interference frequency
suppression
02h
01h
3105h
06h
CH0FN
1
Function number channel 0
50h
80h
3106h
07h
CH0FO
1
Function option channel 0
00h
80h
3107h
08h
CH0UL
2
Upper limit value channel 0
7FFFh
80h
3108h...
3109h
09h
CH0LL
2
Lower limit value channel 0
8000h
80h
310Ah...
310Bh
0Ah
CH1FN
1
Function number channel 1
50h
81h
310Ch
0Bh
CH1FO
1
Function option channel 1
00h
81h
310Dh
0Ch
CH1UL
2
Upper limit value channel 1
7FFFh
81h
310Eh...
310Fh
0Dh
CH1LL
2
Lower limit value channel 1
8000h
81h
3110h...3111h 0Eh
CH2FN
1
Function number channel 2
50h
2
82h
3112h
0Fh
CH2FO
1
Function option channel 2
00h
82h
3113h
10h
CH2UL
2
Upper limit value channel 2
7FFFh
82h
3114h...
3115h
11h
CH2LL
2
Lower limit value channel 2
8000h
82h
3116h...
3117h
12h
CH3FN
1
Function number channel 3
50h
2
83h
3118h
13h
CH3FO
1
Function option channel 3
00h
83h
3119h
14h
CH3UL
2
Upper limit value channel 3
7FFFh
83h
311Ah...
311Bh
15h
CH3LL
2
Lower limit value channel 3
8000h
83h
311Ch...
311Dh
16h
1) This record set may only be transferred at STOP state.
2) with 2 channel operation FFh
VIPA System SLIO
Analog Input
031-1BD80 - AI 4x16Bit R/RTD > Parameter data
HB300 | SM-AIO | | en | 17-05
142