For wires with a cross section of 0.08mm
2
up to 1.5mm
2
.
Pos.
Function
Type
Description
1
AO 0
O
Channel 0
2
AGND
O
Ground channels
3
AO 2
O
Channel 2
4
AGND
O
Ground channels
5
AO 1
O
Channel 1
6
AGND
O
Ground channels
7
AO 3
O
Channel 3
8
AGND
O
Ground channels
O: Output
No byte of the input area is used by the module.
At CPU, PROFIBUS and PROFINET the output area is embedded to the corresponding
address area.
IX - Index for access via CANopen with s = Subindex, depends on number and type of
analog modules
SX - Subindex for access via EtherCAT with Index 7000h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Addr.
Name
Bytes
Function
IX
SX
+0
AO 0
2
Analog value channel 0
6411h/s
01h
+2
AO 1
2
Analog value channel 1
6411h/s+1
02h
+4
AO 2
2
Analog value channel 2
6411h/s+2
03h
+6
AO 3
2
Analog value channel 3
6411h/s+3
04h
Pin assignment
Input area
Output area
VIPA System SLIO
Analog Output
032-1CD70 - AO 4x16Bit ±10V
HB300 | SM-AIO | | en | 17-05