Measuring range
(funct. no.)
Measuring value
Signal range
Range
---
---
underrange
3 wire: 0 ... 3000
W
(DAh)
3528
W
32511
overrange
0 ... 3000
W
0 ... 27648
nominal range
---
---
underrange
4 wire: 0 ... 60
W
(E0h)
70.55
W
32511
overrange
0 ... 60
W
0 ... 27648
nominal range
---
---
underrange
4 wire: 0 ... 600
W
(E1h)
705.5
W
32511
overrange
0 ... 600
W
0 ... 27648
nominal range
---
---
underrange
4 wire: 0 ... 3000
W
(E2h)
3528
W
32511
overrange
0 ... 3000
W
0 ... 27648
nominal range
---
---
underrange
Temperature
Measuring range
(funct. no.)
Measuring value
in °C
(0.1°C/digit)
Measuring value in
°F
(0.1°F/digit)
Measuring value in K
(0.1K/digit)
Range
Type J:
[Fe-Cu-Ni IEC]
-210 ... +1200°C
-346 ... 2192°F
63.2 ... 1473.2K
(B0h: ext. comp. 0°C)
(C0h: int. comp. 0°C)
+14500
26420
17232
overrange
-2100 ... +12000
-3460 ... 21920
632 ... 14732
nominal range
---
---
---
underrange
Type K:
[Ni-Cr-Ni]
-270 ... +1372°C
-454 ... 2501.6°F
0 ... 1645.2K
(B1h: ext. comp. 0°C)
(C1h: int. comp. 0°C)
+16220
29516
18952
overrange
-2700 ... +13720
-4540 ... 25016
0 ... 16452
nominal range
---
---
---
underrange
Type N:
[Ni-Cr-Si]
-270 ... +1300°C
-454 ... 2372°F
+15500
28220
18232
overrange
-2700 ... +13000
-4540 ... 23720
0 ... 15732
nominal range
VIPA System SLIO
Analog Input
Measuring ranges and function numbers
HB300 | SM-AIO | | en | 17-05
44