Name
Bytes
Function
Default
DS
IX
SX
CH0FN
1
Function number channel 0
10h
80h
3100h
01h
CH1FN
1
Function number channel 1
10h
81h
3101h
02h
CH2FN
1
Function number channel 2
10h
82h
3102h
03h
CH3FN
1
Function number channel 3
10h
83h
3103h
04h
In the following there are the measuring ranges with corresponding function number
listed, which were supported by the analog module. With FFh the corresponding channel
is deactivated. The formulas listed here allow you to transform an evaluated measuring
value (digital value) to a value assigned to the measuring range (analog value) and vice
versa.
Meas. range
(funct. no.)
Voltage
(U)
Decimal
(D)
Hex
Range
Formulas
0 ... 10V
Siemens S7 format
(10h)
11.76V
32511
7EFFh
overrange
10V
27648
6C00h
nominal range
5V
13824
3600h
0V
0
0000h
-1.76V
-4864
ED00h
underrange
0 ... 10V
Siemens S5 format
(20h)
12.5V
20480
5000h
overrange
10V
16384
4000h
nominal range
5V
8192
2000h
0V
0
0000h
-2V
-3277
F333h
underrange
3.10.3
Diagnostic data
So this module does not support diagnostic interrupt functions, the diagnostics data serve
for information about this module. On error the corresponding channel LED of the module
is activated and the error is registered in the diagnostics data.
The following errors are listed in the diagnostics data:
n
Error in project engineering / parameterization
n
Measuring range overflow
n
Measuring range underflow
DS - Record set for access via CPU, PROFIBUS and PROFINET. The access happens
by DS 01h. Additionally the first 4 bytes may be accessed by DS 00h.
IX - Index for access via CANopen. The access happens by IX 2F01h. Additionally the
first 4 bytes may be accessed by IX 2F00h.
SX - Subindex for access via EtherCAT with Index 5005h.
More can be found in the according manual of your bus coupler.
CHxFN Function number
channel x
0 ... 10V
VIPA System SLIO
Analog Input
031-1BD30 - AI 4x12Bit 0...10V > Diagnostic data
HB300 | SM-AIO | | en | 17-05