CAUTION!
No use with System SLIO safety modules!
The simultaneous use of 031-1PA00 modules and System SLIO safety
modules on the backplane bus is not permitted!
CAUTION!
Use only with terminal module 001-0AA40!
Please consider that the electronic module AI1x 3Ph 230/400V 1A may
only be used at the terminal module 001-0AA40!
CAUTION!
Line voltage max. 400V!
The line voltage at a voltage connector must not exceed 400V!
CAUTION!
Do not exchange current and voltage connections!
Please note when connecting, that the current and voltage paths are not
exchanged! The module will be destroyed by directly connecting one
phase to a low-resistance current connector!
CAUTION!
Use current transformer with max. 1A!
You may only use current transformer with max. current of 1A! Please
consider the data sheet of your current transformer!
CAUTION!
Note characteristics of current transformers!
–
Please consider the data sheet of your current transformer!
–
Some current transformer must not be operated in idle mode!
–
Before commissioning your module must be connected to the secon-
dary winding of the current transformer!
CAUTION!
All phases of one supply grid!
Please note that the phases to be measured must be from the same
supply grid!
VIPA System SLIO
Analog Input
031-1PA00 - AI1x 3Ph 230/400V 1A > Safety precautions