4.15.1
Technical data
Order no.
032-1CD70
Type
SM 032
Module ID
050A 2560
Current consumption/power loss
Current consumption from backplane bus
65 mA
Power loss
0.8 W
Technical data analog outputs
Number of outputs
4
Cable length, shielded
200 m
Rated load voltage
DC 24 V
Reverse polarity protection of rated load voltage
ü
Current consumption from load voltage L+ (without load)
-
Voltage output short-circuit protection
ü
Voltage outputs
ü
Min. load resistance (voltage range)
5 kΩ
Max. capacitive load (current range)
1 µF
Max. inductive load (current range)
10 mA
Output voltage ranges
-10 V ... +10 V
0 V ... +10 V
Operational limit of voltage ranges
+/-0.2%
Basic error limit voltage ranges
+/-0.1%
Destruction limit against external applied voltage
max. 24V
Current outputs
-
Max. in load resistance (current range)
-
Max. inductive load (current range)
-
Typ. open circuit voltage current output
-
Output current ranges
-
Operational limit of current ranges
-
Basic error limit current ranges
-
Destruction limit against external applied voltage
-
Settling time for ohmic load
150 µs
Settling time for capacitive load
2 ms
Settling time for inductive load
-
Resolution in bit
16
Conversion time
200 µs all channels
Substitute value can be applied
no
VIPA System SLIO
Analog Output
032-1CD70 - AO 4x16Bit ±10V > Technical data
HB300 | SM-AIO | | en | 17-05
435