Meas. range
(funct. no.)
Voltage
(U)
Decimal
(D)
Hex
Range
Formulas
0 ... 10V
Siemens S7 format
(10h)
11.76V
32511
7EFFh
overrange
10V
27648
6C00h
nominal range
5V
13824
3600h
0V
0
0000h
-1.76V
-4864
ED00h
underrange
0 ... 10V
Siemens S5 format
(20h)
12.5V
20480
5000h
overrange
10V
16384
4000h
nominal range
5V
8192
2000h
0V
0
0000h
-2V
-3277
F333h
underrange
For each channel an
upper
and a
lower limit
may be defined. Here only values of the
nominal range may be preset, otherwise you receive a parameterization error. By preset-
ting 7FFFh for the upper respectively 8000h for the lower limit value the corresponding
limit is deactivated. As soon as the measuring value is beyond the limits and the limit
value monitoring is activated, a process interrupt is initialized.
3.24.3
Diagnostics and interrupt
Event
Process interrupt
Diagnostics interrupt
parameterizable
Error in project
engineering/
parameterization
-
X
-
Measuring range overflow
-
X
-
Measuring range underflow
-
X
-
Limit overflow
X
-
X
Limit underflow
X
-
X
Diagnostic buffer overflow
-
X
-
Communication error
-
X
-
Process interrupt lost
-
X
-
So you may react to asynchronous events, there is the possibility to activate a process
interrupt. A process interrupt interrupts the linear program sequence and jumps
depending on the master system to a corresponding Interrupt routine. Here you can react
to the process interrupt accordingly.
With CANopen the process interrupt data a transferred via an emergency telegram.
Operating with CPU, PROFIBUS and PROFINET the process interrupt data were trans-
ferred via diagnostics telegram.
0 ... 10V
CHxUL CHxLL Upper limit
value Lower limit value
channel x
Process interrupt
VIPA System SLIO
Analog Input
031-1CD70 - AI 4x16Bit ±10V > Diagnostics and interrupt
HB300 | SM-AIO | | en | 17-05