For wires with a cross section of 0.08mm
2
up to 1.5mm
2
.
Pos.
Function
Type
Description
1
+AI 0
I
+ Channel 0
2
-AI 0
I
Ground Channel 0
3
+AI 2
I
+ Channel 2
4
-AI 2
I
Ground Channel 2
5
+AI 1
I
+ Channel 1
6
-AI 1
I
Ground Channel 1
7
+AI 3
I
+ Channel 3
8
-AI 3
I
Ground Channel 3
I: Input
If a 2wire measuring transducer is used, you have to connect in line an
external power supply.
At CPU, PROFIBUS and PROFINET the input respectively output area is embedded to
the corresponding address area.
IX - Index for access via CANopen with s = Subindex, depends on number and type of
analog modules
SX - Subindex for access via EtherCAT with Index 6000h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Addr.
Name
Bytes
Function
IX
SX
+0
AI 0
2
Analog value channel 0
6401h/s
01h
+2
AI 1
2
Analog value channel 1
6401h/s+1
02h
Pin assignment
In-/Output area
Input area
VIPA System SLIO
Analog Input
031-1CD45 - AI 4x16Bit 0(4)...20mA
HB300 | SM-AIO | | en | 17-05
257