3.4.2 Parameter data
DS - Record set for access via CPU, PROFIBUS and PROFINET
IX - Index for access via CANopen
SX - Subindex for access via EtherCAT with Index 3100h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Name
Bytes
Function
Default
DS
IX
SX
DIAG_EN
1
Diagnostics*
00h
00h
3100h
01h
SHORT_EN
1
Monitoring of sensor voltage*
00h
00h
3101h
02h
LIMIT_EN
1
Limit value monitoring*
00h
00h
3102h
03h
RES
1
reserved*
00h
00h
3103h
04h
CH0FN
1
Function number channel 0
31h
80h
3104h
05h
CH0FO
1
Function option channel 0
00h
80h
3105h
06h
CH0UL
2
Upper limit value channel 0
7FFFh
80h
3106h...
3107h
07h
CH0LL
2
Lower limit value channel 0
8000h
80h
3108h...
3109h
08h
CH1FN
1
Function number channel 1
31h
81h
310Ah
09h
CH1FO
1
Function option channel 1
00h
81h
310Bh
0Ah
CH1UL
2
Upper limit value channel 1
7FFFh
81h
310Ch...
310Dh
0Bh
CH1LL
2
Lower limit value channel 1
8000h
81h
310Eh...
310Fh
0Ch
* This record set may only be transferred at STOP state.
Byte
Bit 7 ... 0
0
n
Diagnostic interrupt
–
00h: disabled
–
40h: enabled
n
Here you can enable respectively disable the diagnostic interrupt.
Byte
Bit 7 ... 0
0
n
Bit 0: Monitoring of sensor voltage channel 0 (1: on)
n
Bit 1: Monitoring of sensor voltage channel 1 (1: on)
n
Bit 7 ... 2: reserved
Byte
Bit 7 ... 0
0
n
Bit 0: Limit value monitoring channel 0 (1: on)
n
Bit 1: Limit value monitoring channel 1 (1: on)
n
Bit 7 ... 2: reserved
DIAG_EN Diagnostic inter-
rupt
SHORT_EN Monitoring
sensor voltage
LIMIT_EN Limit value
monitoring
VIPA System SLIO
Analog Input
031-1BB10 - AI 2x12Bit 0(4)...20mA - ISO > Parameter data
HB300 | SM-AIO | | en | 17-05
52