Byte
Bit 7 ... 0
0
n
Bit 1, 0: Interference frequency suppression channel 0
–
00: deaktiviert
–
01: 60Hz
–
10: 50Hz
n
Bit 3, 2: Interference frequency suppression channel 1
–
00: deaktiviert
–
01: 60Hz
–
10: 50Hz
n
Bit 7 ... 4: reserved
In the following there are the measuring ranges with function number listed, which were
supported by the analog module. With FFh the corresponding channel is deactivated. The
formulas listed here allow you to transform an evaluated measuring value (digital value)
to a value assigned to the measuring range (analog value) and vice versa.
Meas. range
(funct. no.)
Voltage
(U)
Decimal
(D)
Hex
Range
Formulas
0 ... 10V
Siemens S7 format
(10h)
11.76V
32511
7EFFh
overrange
10V
27648
6C00h
nominal range
5V
13824
3600h
0V
0
0000h
-1.76V
-4864
ED00h
underrange
0 ... 10V
Siemens S5 format
(20h)
12.5V
20480
5000h
overrange
10V
16384
4000h
nominal range
5V
8192
2000h
0V
0
0000h
-2V
-3277
F333h
underrange
For each channel an
upper
and a
lower limit
may be defined. Here only values of the
nominal range may be preset, otherwise you receive a parameterization error. By preset-
ting 7FFFh for the upper respectively 8000h for the lower limit value the corresponding
limit is deactivated. As soon as the measuring value is beyond the limits and the limit
value monitoring is activated, a process interrupt is initialized.
3.17.3
Diagnostics and interrupt
Event
Process
interrupt
Diagnostics
interrupt
parameterizable
Error in project
engineering/parameterization
-
X
-
Measuring range overflow
-
X
-
SUPR Interference fre-
quency suppression
CHxFN Function number
channel x
0 ... 10V
CHxUL CHxLL Upper limit
value Lower limit value
channel x
VIPA System SLIO
Analog Input
031-1CB30 - AI 2x16Bit 0...10V > Diagnostics and interrupt
HB300 | SM-AIO | | en | 17-05