In the following there are the measuring ranges with corresponding function number
listed, which were supported by the analog module. With FFh the corresponding channel
is disabled and disabled the respective sensor supply. The formulas listed here allow you
to transform an evaluated measuring value (digital value) to a value assigned to the
measuring range (analog value) and vice versa.
Meas. range
(funct. no.)
Current
(I)
Decimal
(D)
Hex
Range
Formulas
0 ... 20mA
Siemens
S7 format
(31h)
23.52mA
32511
7EFFh
overrange
20mA
27648
6C00h
nominal range
10mA
13824
3600h
0mA
0
0000h
-3.52mA
-4864
ED00h
underrange
0 ... 20mA
Siemens
S5 format
(41h)
25.00mA
20480
5000h
overrange
20mA
16384
4000h
nominal range
10mA
8192
2000h
0mA
0
0000h
-4,00mA
-3277
F333h
underrange
4 ... 20mA
Siemens
S7 format
(30h)
22.81mA
32511
7EFFh
overrange
20mA
27648
6C00h
nominal range
12mA
13824
3600h
4mA
0
0000h
1.19mA
-4864
ED00h
underrange
4 ... 20mA
Siemens
S5 format
(40h)
24.00mA
20480
5000h
overrange
20mA
16384
4000h
nominal range
12mA
8192
2000h
4mA
0
0000h
0.8mA
-3277
F333h
underrange
0 ... 20mA / 4KM format
Meas. range
(funct. no.)
Current
(I)
Decimal
(D)
Hex
Range
Formulas
0 ... 20mA
4KM format
(3Fh)
20.457mA
4095
0FFFh
overrange
20mA
4000
0FA0h
nominal range
10mA
2000
07D0h
0mA
0
0000h
---
underrange
CHxFN Function number
channel x
0(4) ... 20mA
VIPA System SLIO
Analog Input
031-1BB10 - AI 2x12Bit 0(4)...20mA - ISO > Parameter data