Output range
(funct. no.)
Voltage
(U)
Decimal
(D)
Hex
Range
Formulas
±10V
Siemens S format
(12h)
11.76V
32511
7EFFh
overrange
10V
27648
6C00h
nominal range
5V
13824
3600h
0V
0
0000h
-5V
-13824
CA00h
-10V
-27648
9400h
-11.76V
-32512
8100h
underrange
±10V
Siemens S5 format
(22h)
12.5V
20480
5000h
overrange
10V
16384
4000h
nominal range
5V
8192
2000h
0V
0
0000h
-5V
-8192
E000h
-10V
-16384
C000h
-12.5V
-20480
B000h
underrange
Output range
(funct. no.)
Voltage
(U)
Decimal
(D)
Hex
Range
Formulas
0 ... 10V
Siemens
S7 format
(10h)
11,76V
32511
7EFFh
overrange
10V
27648
6C00h
nominal range
5V
13824
3600h
0V
0
0000h
Not possible, is limited to 0V.
underrange
0 ... 10V
Siemens
S5 format
(20h)
12,5V
20480
5000h
overrange
10V
16384
4000h
nominal range
5V
8192
2000h
0V
0
0000h
Not possible, is limited to 0V.
underrange
4.15.3
Diagnostic data
So this module does not support diagnostic interrupt functions, the diagnostics data serve
for information about this module. On error the corresponding channel LED of the module
is activated and the error is registered in the diagnostics data.
±10V
0 ... 10V
VIPA System SLIO
Analog Output
032-1CD70 - AO 4x16Bit ±10V > Diagnostic data
HB300 | SM-AIO | | en | 17-05
438