Name
Bytes
Function
Default
DS
IX
SX
SUPR
1
Interference frequency suppression
00h
01h
3100h
01h
CH0FN
1
Function number channel 0
10h
80h
3101h
02h
CH1FN
1
Function number channel 1
10h
81h
3102h
03h
CH2FN
1
Function number channel 2
10h
82h
3103h
04h
CH3FN
1
Function number channel 3
10h
83h
3104h
05h
Byte
Bit 7 ... 0
0
n
Bit 1, 0: Interference frequency suppression channel 0
n
Bit 3, 2: Interference frequency suppression channel 1
n
Bit 5, 4: Interference frequency suppression channel 2
n
Bit 7, 6: Interference frequency suppression channel 3
–
00: deactivated
–
01: 60Hz
–
10: 50Hz
e.g.: 10101010: all channels frequency suppression 50Hz
In the following there are the measuring ranges with corresponding function number
listed, which were supported by the analog module. With FFh the corresponding channel
is deactivated. The formulas listed here allow you to transform an evaluated measuring
value (digital value) to a value assigned to the measuring range (analog value) and vice
versa.
Meas. range
(funct. no.)
Voltage
(U)
Decimal
(D)
Hex
Range
Formulas
0 ... 10V
Siemens S7 format
(10h)
11.76V
32511
7EFFh
overrange
10V
27648
6C00h
nominal range
5V
13824
3600h
0V
0
0000h
-1.76V
-4864
ED00h
underrange
0 ... 10V
Siemens S5 format
(20h)
12.5V
20480
5000h
overrange
10V
16384
4000h
nominal range
5V
8192
2000h
0V
0
0000h
-2V
-3277
F333h
underrange
3.21.3
Diagnostic data
So this module does not support diagnostic interrupt functions, the diagnostics data serve
for information about this module. On error the corresponding channel LED of the module
is activated and the error is registered in the diagnostics data.
SUPR Interference fre-
quency suppression
CHxFN Function number
channel x
0 ... 10V
VIPA System SLIO
Analog Input
031-1CD35 - AI 4x16Bit 0...10V > Diagnostic data
HB300 | SM-AIO | | en | 17-05
240