ID
Description
Data type
Unit
Min. value
Max. value
18
Voltage L1
INT_32
1mV
0
300 000
19
Current L1
INT_16
1mA
0
5 000 000
20
Cos phi L1
*)
INT_8
0.01
-100
100
21
Harmonic voltage L1
INT_32
1mV
0
300 000
22
Harmonic current L1
INT_16
1mA
0
5 000 000
23
Active power L2
INT_32
1mW
-1 250 000
1 250 000
24
Reactive power L2
INT_32
1mW
-1 250 000
1 250 000
25
Total power L2
INT_32
1mW
-1 250 000
1 250 000
26
Voltage L2
INT_32
1mV
0
300 000
27
Current L2
INT_16
1mA
0
5 000 000
28
Cos phi L2
*)
INT_8
0.01
-100
100
29
Harmonic voltage L2
INT_32
1mV
0
300 000
30
Harmonic current L2
INT_16
1mA
0
5 000 000
31
Active power L3
INT_32
1mW
-1 250 000
1 250 000
32
Reactive power L3
INT_32
1mW
-1 250 000
1 250 000
33
Total power L3
INT_32
1mW
-1 250 000
1 250 000
34
Voltage L3
INT_32
1mV
0
300 000
35
Current L3
INT_16
1mA
0
5 000 000
36
Cos phi L3
*)
INT_8
0.01
-100
100
37
Harmonic voltage L3
UINT_32
1mV
0
300 000
38
Harmonic current L3
UINT_16
1mA
0
5 000 000
39
Overflow energy meter
Is incremented by 1 in case of overflow of
the energy meter (ID = 1)
UINT_32
40
Overflow energy meter
Is incremented by 1 in case of overflow of
the energy meter (ID = 2)
UINT_32
41
‘Status measurement’ on page 318
UINT_16
*) The measuring accuracy of the Cos phi is maintained from a minimum current of 5mA x
CT-FACTOR
(current transformer factor).
The display resolution of the energy meter is 1Wh x
CT-FACTOR
(current transformer
factor).
Chapter 3.27.5 ‘Parameter data’ on page 314
The measuring tolerance for each measurand is continuously 1%.
Each measurand one
ID
is assigned. The access to the measured value of a measurand
happens by means of the corresponding
ID
.
Resolution energy meter
Tolerance
ID
VIPA System SLIO
Analog Input
031-1PA00 - AI1x 3Ph 230/400V 1A > Measurands
HB300 | SM-AIO | | en | 17-05