SX - Subindex for access via EtherCAT with Index 5000h
More can be found in the according manual of your bus coupler.
Name
Bytes
Function
Default
SX
PRIT_OL
1
Limit overflow channel x
00h
02h
PRIT_UL
1
Limit underflow channel x
00h
03h
PRIT_US
2
µs ticker
00h
04h ... 05h
Byte
Bit 7 ... 0
0
n
Bit 0: Limit overflow channel 0
n
Bit 1: Limit overflow channel 1
n
Bit 7 ... 2: reserved
Byte
Bit 7 ... 0
0
n
Bit 0: Limit underflow channel 0
n
Bit 1: Limit underflow channel 1
n
Bit 7 ... 2: reserved
Byte
Bit 7 ... 0
0 ... 1
Value of the µs ticker at the moment of the diagnostic.
µs-ticker
In the SLIO module there is a 32 bit timer (µs ticker). With PowerON the timer starts
counting with 0. After 2
32
-1µs the timer starts with 0 again. PRIT_US represents the lower
2 byte of the µs ticker value (0 ... 2
16
-1).
Via the parameterization you may activate a diagnostic interrupt for the module. With a
diagnostics interrupt the module serves for diagnostics data for diagnostic interrupt
incoming
.
As soon as the reason for releasing a diagnostic interrupt is no longer present, the diag-
nostic interrupt
going
automatically takes place. All events of a channel between diagnostic
interrupt
incoming
and diagnostic interrupt
going
are not stored and get lost. Within this time
window (1. diagnostic interrupt
incoming
until last diagnostic interrupt
going
) the MF-LED of the
module is on.
The following errors are listed in the diagnostics data:
n
Error in project engineering / parameterization
n
Measuring range overflow
n
Measuring range underflow
n
Process interrupt lost
n
Power supply failed
PRIT_OL Limit overflow
PRIT_UL Limit underflow
PRIT_US µs ticker
Diagnostic data
VIPA System SLIO
Analog Input
031-1CB70 - AI 2x16Bit ±10V > Diagnostics and interrupt