I
EXC
Supply current
U
EXC
Excitation voltage
R
B
Bridge resistance
n
Number of parallel connections
The following tables show the properties of the sensors for e.g. 2 respectively 3 parallel
connected load cells.
Example
2 parallel
Bridge resistance R
B
Excitation
voltage
U
EXC
60
Ω
175
Ω
350
Ω
500
Ω
2.5V
X
X
X
X
5V
X
X
X
X
7.5V
not possible
X
X
X
10V
not possible
X
X
X
12V
not possible
X
X
X
3 parallel
Bridge resistance R
B
Excitation
voltage
U
EXC
40
Ω
116.7
Ω
233.3
Ω
333.3
Ω
2.5V
X
X
X
X
5V
not possible
X
X
X
7.5V
not possible
X
X
X
10V
not possible
X
X
X
12V
not possible
not possible
X
X
To connect your sensors please always use shielded cables!
Please always use the excitation voltage U
EXC
of the module! The con-
nection of sensors with external power supply is not possible.
3.16.2
In-/Output area
At CPU, PROFIBUS and PROFINET the input respectively output area is embedded to
the corresponding address area.
IX - Index for access via CANopen with s = Subindex, depends on number and type of
analog modules
SX - Subindex for access via EtherCAT with Index 6000h/7000h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
In-/Output area
VIPA System SLIO
Analog Input
031-1CA20 - AI 1x16(24)Bit Strain gauge (DMS) > In-/Output area