3.23.2
Parameter data
DS - Record set for access via CPU, PROFIBUS and PROFINET
IX - Index for access via CANopen
SX - Subindex for access via EtherCAT with Index 3100h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Name
Bytes
Function
Default
DS
IX
SX
SUPR
1
Interference frequency suppression
00h
01h
3100h
01h
CH0FN
1
Function number channel 0
31h
80h
3101h
02h
CH1FN
1
Function number channel 1
31h
81h
3102h
03h
CH2FN
1
Function number channel 2
31h
82h
3103h
04h
CH3FN
1
Function number channel 3
31h
83h
3104h
05h
Byte
Bit 7 ... 0
0
n
Bit 1, 0: Interference frequency suppression channel 0
n
Bit 3, 2: Interference frequency suppression channel 1
n
Bit 5, 4: Interference frequency suppression channel 2
n
Bit 7, 6: Interference frequency suppression channel 3
–
00: deactivated
–
01: 60Hz
–
10: 50Hz
e.g.: 10101010: all channels frequency suppression 50Hz
In the following there are the measuring ranges with corresponding function number
listed, which were supported by the analog module. With FFh the corresponding channel
is deactivated. The formulas listed here allow you to transform an evaluated measuring
value (digital value) to a value assigned to the measuring range (analog value) and vice
versa.
SUPR Interference fre-
quency suppression
CHxFN Function number
channel x
VIPA System SLIO
Analog Input
031-1CD45 - AI 4x16Bit 0(4)...20mA > Parameter data
HB300 | SM-AIO | | en | 17-05
261