3.27.5
Parameter data
DS - Record set for access via CPU, PROFIBUS and PROFINET
IX - Index for access via CANopen
SX - Subindex for access via EtherCAT with Index 3100h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Name
Data type
Description
Default
(dec.)
DS
IX
SX
CFG
UINT_8
Choice of phases and data formats
0
80h
3100h
01h
F0V1
UINT_8
Frame 0: Value 1 (ID)
1
81h
3101h
02h
F0V2
UINT_8
Frame 0: Value 2 (ID)
9
3102h
03h
F0V3
UINT_8
Frame 0: Value 3 (ID)
13
3103h
04h
F0V4
UINT_8
Frame 0: Value 4 (ID)
0
3104h
05h
F0V5
UINT_8
Frame 0: Value 5 (ID)
0
3105h
06h
IRMS_MAX
UINT_32
Current upper limit [mA]
Range of values: 0 ... 25000000
0
82h
3106h..
3109h
07h
VRMS_MAX
UINT_16
Voltage upper limit [V]
Range of values: 0 ... 500
260
83h
310Ah
310Bh
08h
VRMS_MIN
UINT_16
Voltage lower limit [V]
Range of values: 0 ... 500
200
310Ch..
310Dh
09h
PF_MIN
UINT_8
CosPhi lower limit [0.01]
Range of values: 0 ... 100
30
84h
310Eh..
0Ah
T_MAX
UINT_16
Temperature upper limit [0.01 °C]
Range of values: 0 ... 20000
7000
85h
310Fh..
3110h
0Bh
F_MAX
UINT_16
Frequency upper limit [0.01 Hz]
Range of values: 0 ... 20000
5100
3111h..
3112h
0Ch
F_MIN
UINT_16
Frequency lower limit [0.01 Hz]
Range of values: 0 ... 20000
4900
3113h..
3114h
0Dh
CT_FACTOR
UINT_16
Current transformer factor
Range of values: 1 ... 5000
1
3115h..
3116h
0Eh
HARM
UINT_8
Range of values: 1 ... 30
1
86h
3117h
0Fh
The parameters are transferred in big-endian format (byte order: high byte, low byte).
VIPA System SLIO
Analog Input
031-1PA00 - AI1x 3Ph 230/400V 1A > Parameter data
HB300 | SM-AIO | | en | 17-05