So you may react to asynchronous events, there is the possibility to activate a process
interrupt. A process interrupt interrupts the linear program sequence and jumps
depending on the master system to a corresponding Interrupt routine. Here you can react
to the process interrupt accordingly.
With CANopen the process interrupt data a transferred via an emergency telegram.
Operating with CPU, PROFIBUS and PROFINET the process interrupt data were trans-
ferred via diagnostics telegram.
SX - Subindex for access via EtherCAT with Index 5000h
More can be found in the according manual of your bus coupler.
Name
Bytes
Function
Default
SX
PRIT_OL
1
Upper limit overflow channel x
00h
02h
PRIT_UL
1
Lower limit underflow channel x
00h
03h
PRIT_US
2
µs-Ticker
00h
04h ... 05h
Byte
Bit 7 ... 0
0
n
Bit 0: Upper limit overflow channel 0
n
Bit 1: Upper limit overflow channel 1
n
Bit 7 ... 2: reserved
Byte
Bit 7 ... 0
0
n
Bit 0: Lower limit underflow channel 0
n
Bit 1: Lower limit underflow channel 1
n
Bit 7 ... 2: reserved
Byte
Bit 7 ... 0
0...1
16bit µs value at the moment of the interrupt
µs ticker
In the SLIO module there is a 32 bit timer (µs ticker). With PowerON the timer starts
counting with 0. After 2
32
-1µs the timer starts with 0 again. PRIT_US represents the lower
2 byte of the µs ticker value (0 ... 2
16
-1).
Via the parameterization you may activate a diagnostic interrupt for the module. With a
diagnostics interrupt the module serves for diagnostics data for diagnostic interrupt
incoming
.
As soon as the reason for releasing a diagnostic interrupt is no longer present, the diag-
nostic interrupt
going
automatically takes place. All events of a channel between diagnostic
interrupt
incoming
and diagnostic interrupt
going
are not stored and get lost. Within this time
window (1. diagnostic interrupt
incoming
until last diagnostic interrupt
going
) the MF-LED of the
module is on.
Process interrupt
PRIT_OL upper limit over-
flow
PRIT_UL Limit underflow
PRIT_US µs-Ticker
Diagnostic data
VIPA System SLIO
Analog Input
031-1BB10 - AI 2x12Bit 0(4)...20mA - ISO > Diagnostics and interrupt
HB300 | SM-AIO | | en | 17-05
55