Write Protect
The parameter ‘Write Protect’ is only relevant, if the module is connected
to a head module with an integrated Web server. If the module is parame-
terized via the Web server ‘Write Protect’ must be set to "0", otherwise
the changed parameters will not be used!
In the module you can combine some measurands to one data package (Frame), which
is transferred in one step.
By specifying the
ID
of the corresponding measurand, via
F0V1
...
F0V5
the data areas of
Frame 0 can be defined. Please note that here the user data length of 12 bytes is not
exceeded.
Chapter 3.27.6 ‘Measurands’ on page 316
n
Range of values: 0 ... 41
n
Default:
–
F0V1: 1 (active energy consumer)
–
F0V2: 9 (total active power)
–
F0V3: 13 (total cos
j
)
–
F0V4: 0
–
F0V5: 0
3.27.6
Measurands
ID
Description
Data type
Unit
Min. value
Max. value
1
Counter: Active energy consumer
INT_32
1Wh *
0
4 294 967 295
2
Counter: Active energy producer
INT_32
1Wh *
0
4 294 967 295
3
Counter: Active energy L1 consumer
INT_32
1Wh *
0
4 294 967 295
4
Counter: Active energy L1 producer
INT_32
1Wh *
0
4 294 967 295
5
Counter: Active energy L2 consumer
INT_32
1Wh *
0
4 294 967 295
6
Counter: Active energy L2 producer
INT_32
1Wh *
0
4 294 967 295
7
Counter: Active energy L3 consumer
INT_32
1Wh *
0
4 294 967 295
8
Counter: Active energy L3 producer
INT_32
1Wh *
0
4 294 967 295
9
Total active power
INT_32
1mW
-3 750 000
3 750 000
10
Total reactive power
INT_32
1mW
-3 750 000
3 750 000
11
Total apparent power
INT_32
1mW
-3 750 000
3 750 000
12
Frequency
INT_16
0.01Hz
4600
6400
13
Total Cos phi
*)
INT_8
0.01
-100
100
14
Temperature
INT_16
0.01°C
-2500
8500
15
Active power L1
INT_32
1mW
-1 250 000
1 250 000
16
Reactive power L1
INT_32
1mW
-1 250 000
1 250 000
17
Total power L1
INT_32
1mW
-1 250 000
1 250 000
F0V1 ... F0V5
VIPA System SLIO
Analog Input
031-1PA00 - AI1x 3Ph 230/400V 1A > Measurands