Measuring range
(funct. no.)
Measuring value
Signal range
Range
4 wire: 0 ... 60
W
(E0h)
70.55
W
32511
overrange
0 ... 60
W
0 ... 27648
nominal range
---
---
underrange
4 wire: 0 ... 600
W
(E1h)
705.5
W
32511
overrange
0 ... 600
W
0 ... 27648
nominal range
---
---
underrange
4 wire: 0 ... 3000
W
(E2h)
3528
W
32511
overrange
0 ... 3000
W
0 ... 27648
nominal range
---
---
underrange
Depending on the Interference frequency suppression for each channel the transducer
velocity may be set.
Code*
Velocity (in ms) / channel at Interference frequency suppression
50Hz
60Hz
00h*
324.1
270.5
01h*
164.2
137.2
02h*
84.2
70.5
03h
44.1
37.2
04h
24.2
20.5
05h
14.2
12.2
06h
9.2
8.0
07h
6.6
5.9
08h
4.2
3.8
*) For Code 00h, 01h and 02h the tolerances of the technical data "with interference frequency suppression" are valid.
For each channel an
upper
and a
lower limit
may be defined. Here only values of the
nominal range may be preset, otherwise you receive a parameterization error. By preset-
ting 7FFFh for the upper respectively 8000h for the lower limit value the corresponding
limit is deactivated.
As soon as the measuring value is beyond the limits and the limit value monitoring is acti-
vated, a process interrupt is initialized.
CHxFO Function option
channel x
CHxUL / CHxLL channel x
VIPA System SLIO
Analog Input
031-1BD80 - AI 4x16Bit R/RTD > Parameter data
HB300 | SM-AIO | | en | 17-05
147