Addr.
Name
Bytes
Function
IX
SX
+0
DMS_VAL
4
Measured value
5470h/s
01h
+3
DMS_STAT
1
Status
5471h/s
02h
DMS_VAL measured value (weight value)
Byte 0
Byte 1
Bit number
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
Significance
SG
2
30
2
29
2
28
2
27
2
26
2
25
2
24
2
23
2
22
2
21
2
20
2
19
2
18
2
17
2
16
31Bit+SG
SG
Measured value ...
Byte 2
Byte 3
Bit number
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Significance
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
31Bit+SG
... Measured value
DMS_STAT Status
Addr.
Name
Bytes
Function
+3
DMS_STAT
1
n
Status byte
–
Bit 0: 1 =
Input Freeze
active
–
Bit 1: 1 =
Steady State
active *
–
Bit 2: 1 = Self-calibration is running *
–
Bit 3: 1 = Tara was changed
–
Bit 4: 1 = Error in adjustment
–
Bit 5: 1 = Adjustment was changed
–
Bit 6: reserved
–
Bit 7: 1 = Zero balance respectively reference point set
*) These status bits are set by internal event of the module.
n
Input Freeze
–
In the activated state no measurement values are passed to the digital filter.
–
As long as the command bit is set, this bit remains set.
n
Steady State
–
As soon as a measured value is longer than the time
SSW
within the tolerance
window
SST
, in the status word the
Steady State
bit is set.
–
As soon as this condition is not true, the last measured value is first used, the
comparison timer restarted and the bit is reset.
–
The values
SSW
and
SST
can be specified by the parametrization.
3.16.5 ‘Parameter data’ on page 181
n
Self calibration
–
As long as the self calibration is active, this bit is set.
–
During the self calibration there are two reference values internally measured and
based on this the internal offset & factor are calculated.
–
With the self calibration the internal offset and gain error may be compensated.
–
The calibration interval
CI
can be preset by the parametrization.
Input area
VIPA System SLIO
Analog Input
031-1CA20 - AI 1x16(24)Bit Strain gauge (DMS) > In-/Output area
HB300 | SM-AIO | | en | 17-05