Order no.
031-1LB90
Temperature error internal compensation
1 K
Technical unit of temperature measurement
°C, °F, K
Resolution in bit
16
Measurement principle
Sigma-Delta
Basic conversion time
84.2 ms (50 Hz) 70.5 ms (60 Hz) per channel
Noise suppression for frequency
>90dB at 50Hz (UCM<10V)
Status information, alarms, diagnostics
Status display
yes
Interrupts
yes
Process alarm
no
Diagnostic interrupt
yes, parameterizable
Diagnostic functions
yes
Diagnostics information read-out
possible
Module state
green LED
Module error display
red LED
Channel error display
red LED per channel
Isolation
Between channels
-
Between channels of groups to
-
Between channels and backplane bus
ü
Between channels and power supply
-
Max. potential difference between circuits
-
Max. potential difference between inputs (Ucm)
DC 75 V/ AC 50 V
Max. potential difference between Mana and Mintern
(Uiso)
-
Max. potential difference between inputs and Mana (Ucm)
-
Max. potential difference between inputs and Mintern
(Uiso)
DC 75 V/ AC 50 V
Max. potential difference between Mintern and outputs
-
Insulation tested with
DC 500 V
Datasizes
Input bytes
4
Output bytes
0
Parameter bytes
10
Diagnostic bytes
20
Housing
Material
PPE / PPE GF10
VIPA System SLIO
Analog Input
031-1LB90 - AI 2x16Bit TC > Technical data
HB300 | SM-AIO | | en | 17-05