YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
631
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H5-20
(0B57)
Communication
Parameters Reload
Sets the function to immediately enable updated MEMOBUS/Modbus communications
parameters.
0 : Reload at Next Power Cycle
1 : Reload Now
0
(0, 1)
H5-22
(11CF)
Speed Search from
MODBUS
Enables the MEMOBUS/Modbus communication register Speed Search function (bit0 of
15DFH).
0 : Disabled
1 : Enabled
0
(0, 1)
H5-23
(158D)
BACnet Max Master
Sets the maximum number of master MAC ID to scan to when the drive polls for the next
node (Poll for Master).
7F
(1 - 7F)
H5-24
(3DA0)
BACnet Max Info Frames Sets the maximum number of information frames for BACnet.
3
(1 - 255)
H5-25
(1589)
RUN
Function 5A Register 1
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
0044H (U1-05)
(0000H - FFFFH)
H5-26
(158A)
RUN
Function 5A Register 2
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
0045H (U1-06)
(0000H - FFFFH)
H5-27
(158B)
RUN
Function 5A Register 3
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
0042H (U1-03)
(0000H - FFFFH)
H5-28
(158C)
RUN
Function 5A Register 4
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
0049H (U1-10)
(0000H - FFFFH)
H5-33
(3FB3)
Power-up CALL Alarm
Enables and disables
CALL [Serial Comm Transmission Error]
alarm detection.
0 : Disabled
1 : Enabled
1
(0, 1)
H5-34
(3FB4)
RUN
Comm Error (CE) Go-To-
Frequency
Sets the speed at which the drive will run when
H5-04 = 4 [Communication Error Stop
Method = Run at H5-34]
and there is a
CE
.
0.0 Hz
(0.0 - 400.0 Hz)
H5-35
(3FB5)
RUN
Comm Error (CE) Go-To-
Timeout
When
H5-04 = 4 [Communication Error Stop Method = Run at H5-34]
and a
CE
is
present, the drive will run at the
H5-34 [Comm Error (CE) Go-To-Frequency]
speed for
this length of time before it triggers a
CE
fault.
Note:
Set this parameter to 0 s to disable the time-out.
0 s
(0 - 6000 s)
H5-36
(3FB6)
CE Fault Restart Select
Sets the drive to restart (
L5-01 [Number of Auto-Restart Attempts]
) after a
CE
fault.
0 : No Retry
1 : Retry
0
(0, 1)
◆
H7: Virtual MFIO selection
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H7-00
(116F)
Expert
Virtual MFIO selection
Sets the function to enable and disable the virtual I/O function. Set this parameter to 1 to
operate the virtual I/O function.
0 : Disabled
1 : Enabled
0
(0, 1)
H7-01
(1185)
Expert
Virtual Multi-Function
Input 1
Sets the function that enters the virtual input set in
H7-10 [Virtual Multi-Function Output
1]
.
Note:
Settings
1B [Programming Lockout]
and
11B [!Programming Lockout]
are not
available.
F
(1 - 1B8)
H7-02
(1186)
Expert
Virtual Multi-Function
Input 2
Sets the function that enters the virtual input set in
H7-12 [Virtual Multi-Function Output
2]
.
Note:
Settings
1B [Programming Lockout]
and
11B [!Programming Lockout]
are not
available.
F
(1 - 1B8)
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...