252
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■
E2-05: Motor Line-to-Line Resistance
No.
(Hex.)
Name
Description
Default
(Range)
E2-05
(0312)
Motor Line-to-Line
Resistance
Sets the line-to-line resistance for the motor stator windings.
Determined by o2-04
(0.000 - 65.000 Ω)
Note:
This value is the motor line-to-line resistance. Do not set this parameter with the resistance per phase.
Auto-Tuning automatically sets this parameter. If you cannot do Auto-Tuning, use the test report from the motor
manufacturer to configure the settings. You can calculate the motor line-to-line resistance with one of these formulas:
•
E-type insulation: [the resistance value (Ω) shown on the test report at 75 °C] × 0.92
•
B-type insulation: [the resistance value (Ω) shown on the test report at 75 °C] × 0.92
•
F-type insulation: [the resistance value (Ω) shown on the test report at 115 °C] × 0.87
■
E2-06: Motor Leakage Inductance
No.
(Hex.)
Name
Description
Default
(Range)
E2-06
(0313)
Motor Leakage Inductance
Sets the voltage drop from motor leakage inductance when the motor is operating at the rated
frequency and rated current. This value is a percentage of Motor Rated Voltage.
Determined by o2-04
(0.0 - 60.0%)
The drive automatically sets this parameter during Auto-Tuning.
Note:
The motor nameplate does not usually show the quantity of voltage drop. If you do not know the value of the motor leakage inductance,
contact the motor manufacturer to receive a copy of the motor test report.
■
E2-10: Motor Iron Loss
No.
(Hex.)
Name
Description
Default
(Range)
E2-10
(0317)
Motor Iron Loss
Sets the motor iron loss.
Determined by o2-04
(0 - 65535 W)
■
E2-11: Motor Rated Power
No.
(Hex.)
Name
Description
Default
(Range)
E2-11
(0318)
Motor Rated Power
Sets the motor rated output in the units from
o1-58 [Motor Power Unit Selection]
.
Determined by o2-04
(0.00 - 650.00 HP)
The drive automatically sets this parameter to the value input for
“
Motor Rated Power
”
during Auto-Tuning.
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...